Cummins Prime/Standby Power Rating Warranty
Standby Power Rating
Engines of this rating are applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating.
Under no condition is an Engine allowed to operate in parallel with the public utility at the Standby Power rating. This rating should be applied where'reliable utility power is available. A Standby rated Engine is to be sized for a maximum of an 80 percent average load factor and 200 hours of operation per year. This includes less than. 25 hours per year at the Standby Power rating. Standby rating should never be applied except in true emergency power outages. Negotiated power outages contracted with a utility company are not considered an emergency.
Unlimited Time Running Prime Power Rating
Engines with this rating are available for an unlimited number of hours per year in a variable load application, Variable load is not to exceed a 70 percent average of the Prime Power rating during any operating period of 250 hours. Total operating time at 100 percent Prime Power shall not exceed 500 hours per year.
A 10 percent overload capability is available for a period of one hour within a twelve hour period of operation. Total operating time at the 10 percent overload power shall not exceed 25 hours per year.
Limited Time Running Prime Power Rating
Engines of this rating are available for a limited number of hours in a non-variable load application. It is intended for use in situations where power outages are contracted, such as in utility power curtailment. Engines may be operated in parallel to the public utility up to 750 hours per year at power levels never to exceed the Prime Power rating.
Limited Time Running Prime Power ratings differ from Unlimited Time Running in that even though the maximum power output of the Engines is the same, the Limited Time Running allows the Engine to be parallel to the public utility and run at the full Prime Power rating and must never exceed the Prime Power rating.
Continuous/Base Power Rating
Engines with this rating are available for supplying utility power at a constant 100 percent load for an unlimited number of hours per year. No overload capability is available for this rating.
Continuous/Base Power ratings differ from Unlimited Time Running Prime Power ratings in that the Continuous/Base Load ratings are significantly reduced from the Prime Power ratings. Continuous/Base Load ratings have no load factor or application restrictions.
Coverage
Base Engine Warranty
This Warranty covers any failures of the Engine, under normal use and service, which result from a defect in material or factory workmanship (Warrant-able Failure).
Coverage begins with the sale of the Engine by Cummins and continues for the Duration stated below. The Duration commences either on the date of delivery of the Engine to the first user, or on the date the Engine is first leased, rented or loaned, or when the Engine has been operated for 50 hours, whichever occurs first.
Base Engine Warranty
Duration
Which Occurs First
Rating
Months
Hours
Standby Power
24
400
Unlimited Prime Power
12
Unlimited
Limited Prime Power
12
750
Continuous/Base Power
12
Unlimited
Engine after treatment components included in the Cummins Critical Parts List (CPL) and marked with a Cummins part number are covered under Base Engine Warranty. Additional Coverage is outlined in the Emission Warranty section.
Extended Major Components Warranty
The Extended Major Gomponents Warrant3t covers Warrantable Failures of the Engine cylinder block, camshaft, crankshaft and connecting rods (Covered Parts). Bushing and bearing failures are not covered. This Coverage begins with the expiration of the Base Engine Warranty and continues for the following stated Duration. The Duration commences either on the date of delivery of the Engine to the first user, or on the date the Engine is first leased, rented or loaned, or when the Engine has been operated for 50 hours, whichever occurs first.
Extended Major Components Warranty
Duration
Which Occurs First
Rating
Months
Hours
Standby Power
36
600
Unlimited Prime Power
36
10,000
Limited Prime Power
36
2,250
Continuous/Base Power
36
10,000
Consumer Products
This Warranty on Consumer Products in the United States is a LIMITED Warranty. CUMMINS IS NOT RESPONSIBLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. Any implied Warranties applicable to Consumer Products terminate concurrently with the expiration of the express Warranties applicable to the product. In the United States, some states do not allow the exclusion of incidental or consequential damages, or limitations on how long an implied Warranty lasts, so the limitations or exclusions herein may not apply to you.
These Warranties are made to all Owners in the chain of distribution and Coverage continues to all subsequent Owners until the end of the periods of Coverage.
Note: We are Cummins diesel generator OEM and can provide 24KW to 2400KW diesel generator set with Cummins engine. Contact us: sales@dieselgeneratortech.com